    Product Details

    1492 Series


    Allen Bradley general purpose RCDs from the 1492 series. The RCDs have a Type A tripping characteristic and an instantaneous break time. 2 or 4 pole versions available. All the RCDs incorporate screw terminals and can be DIN Rail mounted.

    Features & Benefits


    2 or 4 pole versions
    DIN Rail mount
    Screw Terminals

    Allen Bradley RCD, IP20-Rated Terminals, DIN Rail Mounting - 1492-RCDA4C63


    Improve electrical safeguarding with this RCD from Rockwell Automation's Allen Bradley range. Sensitive 300mA tripping means it detects small-to-moderate leakage currents and quickly redirects them to the ground. This minimises the risk of injury to users and stops short-circuit faults from developing. As a 4-pole component, you can use it to protect several circuits at once, so it's practical for use in busy industrial setups. To ensure safety when handling, the unit's IP20-rated terminals are touch-safe and its IP40-rated housing resists objects such as wires. An impulse withstand voltage of 4kV indicates this RCD effectively shields you and your equipment against significant surge voltages.

    • Ambient temperature range of -25°C to +55°C so suitable for use in harsh environments
    • Push button for easy device testing
    • Screw terminals make secure physical and electrical connections
    • Easy to reset via a simple front toggle switch

    Standards and Certifications


    • VDE
    • CE
    • UL
    • CCC
    • EN

    What does this device's type-A tripping mean?


    This RCD's type-A tripping characteristics mean it activates when it receives two to three times its 63A current rating. This sensitivity make it handy for use with residual AC currents and pulsating DC currents, so it's a versatile component.


    Allen Bradley RCBs

    Specification

    AttributeValue
    Circuit Breaker TypeRCD
    Current Rating63A
    Number of Poles3P+N
    Trip Sensitivity300mA
    Tripping CharacteristicsType A
    Series1492-RCDA
    Standards MetIEC/EN 61008, UL 1053
    Overall Depth75mm
    Rated AC Voltage230 V, 400V
    Mounting StyleDIN Rail Mount
    Overall Length70mm
    Terminal Contact TypeScrew
    Reset Actuator TypeToggle Switch
    Overall Dimensions70 x 88 x 75mm
    Breaking Capacity at Maximum Voltage Rating1 (Residual) kA, 10 (Short-Circuit) kA
    Overall Width88mm