Siemens SIMATIC Series Base for Use with ET 200SP

Subtotal (1 pack of 10 units)*

R 7 047,63

(exc. VAT)

R 8 104,77

(inc. VAT)

Add to Basket
Select or type quantity
In Stock
  • 40 unit(s) ready to ship from another location
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
Per Pack*
10 +R 704.763R 7,047.63

*price indicative

RS stock no.:
203-4115
Mfr. Part No.:
6ES7193-6BP00-2DA0
Manufacturer:
Siemens
Find similar products by selecting one or more attributes.
Select all

Brand

Siemens

Accessory Type

Base Unit

Product Type

Base

Series

SIMATIC

For Use With

ET 200SP

Hazardous Area Certification

No

Standards/Approvals

No

Communication Protocol

I/O

COO (Country of Origin):
DE

Siemens SIMATIC Series Base, 24V Rated Value, 1 Slot - 6ES7193-6BP00-2DA0


This base provides a Compact, non-hazardous area mounting solution for modular I/O installations within automation racks. It functions as the foundational accessory for ET 200SP configurations, offering integrated filtering and potential group separation for controlled distribution of signals and power. The unit is intended for use where standard I/O communication and Compact slotting are required and carries CE, EAC and UKCA approvals.

Features and Benefits:


• 10A max P1/P2 bus current capacity delivers higher peripheral feeding capability
• 2A max process Terminal current protects field devices from overload
• Push-in Terminals allow rapid, tool-free conductor insertion
• Isolation tested at 707VDC ensures electrical separation confidence
• New potential group formation simplifies potential management

Applications


• Suitable for Compact distributed I/O installations with ET 200SP
• Used with I/O modules requiring a single A0 slot configuration
• Ideal for systems needing integrated mains filtering for supply lines
• Can be used for installations up to 5000 m altitude with restrictions
• Used for setups where no auxiliary terminals are required

What conductor sizes are supported for field wiring?


Conductors from 0.14 mm² up to 2.5 mm² (AWG26 to AWG14) are accepted.

How is external power protection handled?


The supply should be protected by a 24 V DC/10 A miniature circuit breaker with B or C tripping characteristic.

Does the unit provide integrated EMI suppression?


Yes, a mains filter is integrated to reduce interference on the supply.

Which Terminal connections link to the internal bus?


Two terminals provide connections to the P1 and P2 bus for backplane communication.