RS PRO HFS5002C2 Series White 2.5 mm² Hook Up Wire, 14 AWG, 2, 100 m, Thermoplastic

Subtotal (1 reel of 100 metres)*

R 10 368,17

(exc. VAT)

R 11 923,40

(inc. VAT)

Add to Basket
Select or type quantity
Stock information currently inaccessible - Please check back later
Reel(s)
Per Reel
Per Metre*
1 +R 10,368.17R 103.682

*price indicative

RS stock no.:
606-098
Manufacturer:
RS PRO
Find similar products by selecting one or more attributes.
Select all

Brand

RS PRO

Cross Sectional Area

2.5 mm²

Product Type

Hook Up Wire

Jacket Colour

White

American Wire Gauge

14AWG

Core Strands

2

Cable Length

100m

Voltage

500 V

Maximum Operating Temperature

70°C

Conductor Material

Annealed Copper

Standards/Approvals

BASEC, BS 5839-1 Cus26.2d, BS 6387:2013 (Categories C,W,Z), BS 7629-1, BS EN 60332-1-2, BS EN 60754-1, BS EN 61034-2, EN 50200:2015, EN 50200:2015 Annex E, LPCB, RoHS

Cable Type

Fire Performance

Jacket Material

Thermoplastic

Minimum Operating Temperature

-15°C

Fire Behaviour

BS EN 61034-2 (Smoke Density), BS 6387:2013, BS EN 60332-1-2, BS EN 60754-1 (Emission of Acid Gas), Dangerous Gases, Resistance to Fire, Smoke

Series

HFS5002C2

COO (Country of Origin):
GB

Firesure 500 2C 2.5mm2 BS7629-1


The RS Pro Fire performance cable is specifically designed for fire detection, alarms, emergency lighting, and voice communication, ensuring functionality during fire, mechanical impact, and water conditions for a prescribed period, supporting evacuation and maintaining critical circuits. Suitable for indoor and outdoor applications, it can be directly buried in plaster, clipped to surfaces, or installed on trays. Manufactured with third-party verified copper, it features a CO2 per kg ratio of Less than 1.7:1 (CO2:Cu) it significantly lower than the global average of more than 4.5:1 (CO2:Cu) it resulting in a 2.5 times lower CO2 impact than conventional copper.

Lower carbon footprint

Manufactured using copper with less than 1.7kg co2 per kg as opposed to the global average of copper which is greater than 4.5kg co2 per kg

Basec approved

Lpcb approved

Tape is adhered to the sheath (allows tape and sheath to be removed simultaneously)

Superior earth continuity (pressured sheath allows better contact of tape and cpc)

Prevents transmission of smoke and dangerous gases through the cable (due to tightly pressured sheath resulting in minimal air gaps within the cable)