Fluke 345 Clamp Meter USB, 2kA dc, Max Current 1.4kA ac CAT IV 600 V
- RS stock no.:
- 252-214
- Mfr. Part No.:
- Fluke 345
- Manufacturer:
- Fluke
Discontinued product
Alternatives
This product is not currently available. Here are our alternative recommendations.
Each
R 127 165,86
(exc. VAT)
R 146 240,74
(inc. VAT)
Each
R 19 990,00
(exc. VAT)
R 22 988,50
(inc. VAT)
- RS stock no.:
- 252-214
- Mfr. Part No.:
- Fluke 345
- Manufacturer:
- Fluke
Not Applicable
- COO (Country of Origin):
- CN
Fluke 345 Power Quality Clamp Meter
The Fluke 345 measures a wide range of electrical parameters for troubleshooting power disturbances in single- and three phase electrical loads. With a bright colour display to see waveforms and trends, a low-pass filter to remove high frequency noise, and a high EMC immunity design, the Fluke 345 is ideal for measurements on switching loads such as variable speed drives, electronic lighting and UPS systems.
Clamp-on measurement of ac current up to 1400A rms and dc current up to 2000A without breaking the circuit
Low pass filter ensures the clamp meter is accurate in noisy environments even with distorted waveforms present on electronic loads
Identify intermittent faults by logging any power quality parameter for minutes, or over a month, including harmonics
Direct measurement of dc ripple (%) for battery and dc systems
Analyse and log harmonics digitally or graphically
Inrush current measurement to capture and analyse nuisance tripping, from 3 to 300 seconds
Large backlit colour display of waveforms (scope function) and trends
Balanced 3-phase power measurement capability
Power Log software supplied to view graphs and generate reports on a PC
USB interface
Harmonic analysis: Analyse, display and log harmonics up to the 30th harmonic (40th harmonic for 15Hz to 22Hz)
Verify batteries: Direct measurement of dc ripple (%) for battery and dc systems
EN61010 safety rating: 600V CAT IV / 1000V CAT III rated for use at the service entrance
Low pass filter ensures the clamp meter is accurate in noisy environments even with distorted waveforms present on electronic loads
Identify intermittent faults by logging any power quality parameter for minutes, or over a month, including harmonics
Direct measurement of dc ripple (%) for battery and dc systems
Analyse and log harmonics digitally or graphically
Inrush current measurement to capture and analyse nuisance tripping, from 3 to 300 seconds
Large backlit colour display of waveforms (scope function) and trends
Balanced 3-phase power measurement capability
Power Log software supplied to view graphs and generate reports on a PC
USB interface
Harmonic analysis: Analyse, display and log harmonics up to the 30th harmonic (40th harmonic for 15Hz to 22Hz)
Verify batteries: Direct measurement of dc ripple (%) for battery and dc systems
EN61010 safety rating: 600V CAT IV / 1000V CAT III rated for use at the service entrance
Supplied with
Test Leads, Power Log software on CD-ROM, USB lead, batteries(fitted), mains adaptor, carry case & instructions.
Fluke Power Quality Clamp Meter
The Fluke power quality clamp meter is the ideal meter for commissioning and troubleshooting modern electrical loads. With a bright colour display to analyse the harmonic spectrum, a low-pass filter to remove high-frequency noise, and a high EMC immunity design, the Fluke 345 is ideal for measurements on switching loads such as variable frequency drives, electronic lighting and UPS systems. Additionally, the Hall Effect measurement system makes the measurement of DC possible without the need to break the circuit, and the internal memory enables long-term logging for analysis of trends or intermittent problems. Clamp-on measurement of AC up to 1400A RMS and DC up to 2000A without breaking the circuit. This meter contains test leads, power log software on CD-ROM, USB lead, batteries (fitted), mains adaptor, carry case and instructions.
Features and Benefits
Voltage measurement is 825V AC/DC
Minimum, maximum, average and inrush recording to capture variations automatically
Logs any power quality parameter, including harmonics for minutes or for over a month to help identify intermittent faults
The low-pass filter to smooth out noisy loads and stabilize readings
Verifies batteries with direct measurement of DC ripple (%) for battery and DC systems
Analyses and logs harmonics digitally or graphically
Downloads logged data via USB with Power Log application software making it easy to view trends and screenshots, analyse and create reports
Powers the instrument without using the battery when performing extended logging sessions
Provides built-in three-phase power measurement capability for balanced loads
USB interface
Display HOLD
Operating temperature ranges between 0°C and 50°C
Minimum, maximum, average and inrush recording to capture variations automatically
Logs any power quality parameter, including harmonics for minutes or for over a month to help identify intermittent faults
The low-pass filter to smooth out noisy loads and stabilize readings
Verifies batteries with direct measurement of DC ripple (%) for battery and DC systems
Analyses and logs harmonics digitally or graphically
Downloads logged data via USB with Power Log application software making it easy to view trends and screenshots, analyse and create reports
Powers the instrument without using the battery when performing extended logging sessions
Provides built-in three-phase power measurement capability for balanced loads
USB interface
Display HOLD
Operating temperature ranges between 0°C and 50°C
Applications
Set up and troubleshoot variable frequency drives and UPS systems
Harmonics measurement
Inrush capture
Load studies
Harmonics measurement
Inrush capture
Load studies
Certifications
CE
cCSAus
IEC/EN 61326-1:1997 class B
IEC/EN 61326-1:1997
CAT IV 600V safety rating
cCSAus
IEC/EN 61326-1:1997 class B
IEC/EN 61326-1:1997
CAT IV 600V safety rating
Attribute | Value |
---|---|
Absolute Maximum AC Current Measurement | 1.4kA ac |
Absolute Maximum DC Current Measurement | 2kA dc |
Absolute Maximum AC Voltage Measurement | 825V ac |
Absolute Maximum DC Voltage Measurement | 825V dc |
Model Number | 345 |
Connectivity | USB |
AC Current Measurement Resolution | 10mA |
DC Current Measurement Resolution | 10mA |
Best DC Current Accuracy | ±(1.5% rdg + 5dgts) |
Clamp Meter Type | Power Clamp Meter |
Best AC Current Accuracy | ±(1.5% rdg + 5dgts) |
Best AC Voltage Accuracy | ±(1% rdg + 5dgts) |
Functions Measured | AC Current, AC Voltage, DC Current, DC Voltage, Frequency, Harmonics, Kilowatt Hour, Power, Power Factor, VAR, Voltage |
True RMS | Yes |
Jaw Capacity Busbars | 58mm |
Best DC Voltage Accuracy | ±(1% rdg + 5dgts) |
Length | 300mm |
Power Source | Battery |
Display Type | LCD |
Battery Type | AA |
Safety Category | CAT IV 600 V |
Battery Life | 10 (Backlight On) h, 12 (Backlight Off) h |
Weight | 820g |
Safety Category Voltage | 600V |
DC Voltage Measurement Resolution | 1mV |
Safety Category Level | CAT IV |
Width | 98mm |
AC Voltage Measurement Resolution | 1mV |
Minimum Operating Temperature | 0°C |
Dimensions | 300 x 98 x 52mm |
Height | 52mm |
Maximum Conductor Size | 58mm |
Maximum Operating Temperature | +50°C |