Phoenix Contact, FLT-SEC Lightning Arrester 440V ac Maximum Voltage Rating 10 mA Maximum Surge Current Protective Device
- RS stock no.:
- 185-3087
- Mfr. Part No.:
- 2907260
- Manufacturer:
- Phoenix Contact
Bulk discount available
Subtotal (1 unit)*
R 29 780,19
(exc. VAT)
R 34 247,22
(inc. VAT)
FREE delivery for orders over R 1,500.00
Temporarily out of stock
- Shipping from 06 April 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
|---|---|
| 1 - 4 | R 29,780.19 |
| 5 - 9 | R 29,035.69 |
| 10 - 49 | R 28,164.62 |
| 50 + | R 27,038.04 |
*price indicative
- RS stock no.:
- 185-3087
- Mfr. Part No.:
- 2907260
- Manufacturer:
- Phoenix Contact
Specification
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Phoenix Contact | |
| Suppressor Type | Protective Device | |
| Product Type | Lightning Arrester | |
| Maximum Voltage | 440V ac | |
| Mount Type | DIN Rail | |
| Maximum Surge Current | 10mA | |
| Series | FLT-SEC | |
| Minimum Operating Temperature | -40°C | |
| Maximum Operating Temperature | 80°C | |
| Length | 106.8mm | |
| Standards/Approvals | EN 61643-11, IEC 61643-11 | |
| Depth | 74.5mm | |
| Height | 167mm | |
| Hazardous Area Certification | No | |
| Select all | ||
|---|---|---|
Brand Phoenix Contact | ||
Suppressor Type Protective Device | ||
Product Type Lightning Arrester | ||
Maximum Voltage 440V ac | ||
Mount Type DIN Rail | ||
Maximum Surge Current 10mA | ||
Series FLT-SEC | ||
Minimum Operating Temperature -40°C | ||
Maximum Operating Temperature 80°C | ||
Length 106.8mm | ||
Standards/Approvals EN 61643-11, IEC 61643-11 | ||
Depth 74.5mm | ||
Height 167mm | ||
Hazardous Area Certification No | ||
- COO (Country of Origin):
- DE
Phoenix Contact FLT-SEC-H-T1-3C-440/25-FM Series Lightning Arrester, 106.8X74.5X167mm, DIN Rail Mount - 2907260
This lightning arrester by Phoenix Contact is designed for industrial use, providing surge protection with a maximum voltage rating of 440V AC. It offers a comprehensive solution for protecting electrical systems from voltage surges, ensuring reliable operation in various environments.
Features & Benefits
• Integrated spark gap and surge-proof fuse for enhanced protection
• No need for separate backup fuse due to integrated overcurrent protection
• Suitable for pre-meter areas with zero leakage current
• Easy installation with innovative push-pull locking mechanism
• Low voltage protection level of 2.5kV
• Optical and mechanical status indicator for monitoring
• Designed for DIN rail mounting
Applications
• Protection of 3-phase power supply networks
• Suitable for combined PE and N installations
• Ideal for industrial automation and electrical systems
• Can be used in a variety of power supply networks
Can this lightning arrester be used in high-temperature environments?
It is designed to operate at temperatures ranging from -40°C to +80°C, making it suitable for various industrial settings.
Will this arrester provide protection against voltage surges in a 3-phase power supply network?
Yes, this lightning arrester is specifically engineered for protecting 3-phase power networks with combined PE and N installations.
Is it necessary to have a separate backup fuse when using this surge protection device?
No, the lightning arrester comes with integrated overcurrent protection, eliminating the need for a separate backup fuse.
Related links
- Phoenix Contact, FLT-SEC Lightning Arrester 440V ac Maximum Voltage Rating 10 mA Maximum Surge Current Protective Device
- Phoenix Contact, FLT-SEC Lightning Arrester 264V ac Maximum Voltage Rating 10 mA Maximum Surge Current Protective Device
- Phoenix Contact, FLT-SEC Lightning Surge Protector 440V ac Maximum Voltage Rating 10 mA Maximum Surge Current Protective
- Phoenix Contact, FLT-SEC Lightning Arrester 255V ac Maximum Voltage Rating 37.5 kA Maximum Surge Current Lightning
- Phoenix Contact, FLT-SEC Lightning Arrester 255V ac Maximum Voltage Rating 50 kA Maximum Surge Current Lightning
- Phoenix Contact, FLT-SEC Lightning Arrester 255V ac Maximum Voltage Rating 22.5 kA Maximum Surge Current Lightning
- Phoenix Contact, FLT-SEC Surge Protection Plug 440V ac Maximum Voltage Rating 50 kA Maximum Surge Current Protective
- Phoenix Contact, FLT-SEC Surge Protection Plug 440V ac Maximum Voltage Rating Protective Plug